In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of alternative zeotropic refrigerant mixtures to R-22, on air/refrigerant horizontal enhanced surface tubing is presented. The new alternatives considered in this study are: R-507, R-404A, R-408A, R-40
Boiling characteristics of alternatives to R-502 inside air/refrigerant enhanced surface tubing
โ Scribed by Samuel M. Sami; Daniel E. Desjardins
- Publisher
- John Wiley and Sons
- Year
- 2000
- Tongue
- English
- Weight
- 140 KB
- Volume
- 24
- Category
- Article
- ISSN
- 0363-907X
No coin nor oath required. For personal study only.
โฆ Synopsis
In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of alternative zeotropic refrigerant mixtures to R-502, on air/refrigerant horizontal enhanced surface tubing is presented. The new alternatives considered in this study are: R-507, R-404A, R-407B, and R-408A.
It was evident from the experimental data that R-502 has the lowest heat transfer rate compared to the other blends in the range investigated. Furthermore, it was also quite evident from these data that R-407B has the highest pressure among the blends under investigation. However, at a Reynolds number less than 3.6;10, it appears from the data that R-404A has the lowest pressure drop compared to other refrigerants under investigation.
๐ SIMILAR VOLUMES
In this paper the test results of a performance evaluation of new alternatives; R-407B, R-507, R-408A and R-404A as substitutes to CFC-502 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing under standard ARI conditions. The data demonstrated th
In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of some alternative refrigerants to HCFC-22, on air/refrigerant horizontal enhanced surface tubing, is presented. Correlations have been proposed to predict the heat transfer characteristics such as av
In this paper, the test results of a performance analysis of new alternatives; R-410A, R-507, R-407C, R-408A and R-404A proposed as substitutes to HCFC-22 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing. Performance tests were conducted accord
This work presents the results of an experimental study concerning the heat transfer characteristics of two-phase flow condensation and boiling of tetrary (R-32/R-125/R143a/R134a) refrigerant mixtures inside water/refrigerant horizontal enhanced surface tubing. Heat transfer characteristics such as