โœฆ Synopsis


In this paper, the test results of a performance analysis of new alternatives; R-410A, R-507, R-407C, R-408A and R-404A proposed as substitutes to HCFC-22 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing. Performance tests were conducted according to the ARI/ASHRAE Standards.

The performance data demonstrated that as an interim replacement, the R-404A blend has a superior performance particularly at low temperatures among the proposed blends. Furthermore, the alternatives to R-22 are characterised by high discharge pressure compared to that of R-22. In particular, R-410A has the highest discharge pressure among the blend studied. R-407C has similar discharge temperature to R-22 at temperatures lower than !83C.


๐Ÿ“œ SIMILAR VOLUMES


Heat transfer prediction of air-to-refri
โœ Samuel M. Sami; Julien Grell ๐Ÿ“‚ Article ๐Ÿ“… 2000 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 178 KB ๐Ÿ‘ 2 views

In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of some alternative refrigerants to HCFC-22, on air/refrigerant horizontal enhanced surface tubing, is presented. Correlations have been proposed to predict the heat transfer characteristics such as av

Performance comparative study of new alt
โœ Samuel M. Sami; Daniel E. Desjardins ๐Ÿ“‚ Article ๐Ÿ“… 2000 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 123 KB ๐Ÿ‘ 2 views

In this paper the test results of a performance evaluation of new alternatives; R-407B, R-507, R-408A and R-404A as substitutes to CFC-502 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing under standard ARI conditions. The data demonstrated th

Boiling characteristics of alternatives
โœ Samuel M. Sami; Daniel E. Desjardins ๐Ÿ“‚ Article ๐Ÿ“… 2000 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 140 KB ๐Ÿ‘ 1 views

In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of alternative zeotropic refrigerant mixtures to R-502, on air/refrigerant horizontal enhanced surface tubing is presented. The new alternatives considered in this study are: R-507, R-404A, R-407B, and

Two-phase flow boiling characteristics o
โœ Samuel M. Sami; Daniel E. Desjardins ๐Ÿ“‚ Article ๐Ÿ“… 2000 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 151 KB ๐Ÿ‘ 2 views

In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of alternative zeotropic refrigerant mixtures to R-22, on air/refrigerant horizontal enhanced surface tubing is presented. The new alternatives considered in this study are: R-507, R-404A, R-408A, R-40