In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of some alternative refrigerants to HCFC-22, on air/refrigerant horizontal enhanced surface tubing, is presented. Correlations have been proposed to predict the heat transfer characteristics such as av
Performance analysis of new alternatives to HCFC-22 inside air/refrigerant-enhanced surface tubing
โ Scribed by Samuel M. Sami; Daniel E. Desjardins
- Publisher
- John Wiley and Sons
- Year
- 2000
- Tongue
- English
- Weight
- 126 KB
- Volume
- 24
- Category
- Article
- ISSN
- 0363-907X
No coin nor oath required. For personal study only.
โฆ Synopsis
In this paper, the test results of a performance analysis of new alternatives; R-410A, R-507, R-407C, R-408A and R-404A proposed as substitutes to HCFC-22 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing. Performance tests were conducted according to the ARI/ASHRAE Standards.
The performance data demonstrated that as an interim replacement, the R-404A blend has a superior performance particularly at low temperatures among the proposed blends. Furthermore, the alternatives to R-22 are characterised by high discharge pressure compared to that of R-22. In particular, R-410A has the highest discharge pressure among the blend studied. R-407C has similar discharge temperature to R-22 at temperatures lower than !83C.
๐ SIMILAR VOLUMES
In this paper the test results of a performance evaluation of new alternatives; R-407B, R-507, R-408A and R-404A as substitutes to CFC-502 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing under standard ARI conditions. The data demonstrated th
In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of alternative zeotropic refrigerant mixtures to R-502, on air/refrigerant horizontal enhanced surface tubing is presented. The new alternatives considered in this study are: R-507, R-404A, R-407B, and
In this paper, an experimental study on the heat transfer characteristics of two-phase #ow boiling of alternative zeotropic refrigerant mixtures to R-22, on air/refrigerant horizontal enhanced surface tubing is presented. The new alternatives considered in this study are: R-507, R-404A, R-408A, R-40