๐”– Bobbio Scriptorium
โœฆ   LIBER   โœฆ

Performance of some zeotropic mixtures as alternative refrigerants to R22 and R502

โœ Scribed by G. Venkatarathnam; S. Srinivasa Murthy


Publisher
John Wiley and Sons
Year
1998
Tongue
English
Weight
158 KB
Volume
22
Category
Article
ISSN
0363-907X

No coin nor oath required. For personal study only.

โœฆ Synopsis


Many zeotropic refrigerant mixtures are being proposed as alternatives to CFCs and HFCFs refrigerants that are being phased out. The main advantage in the use of zeotropic mixtures is the possibility of reduction in entropy generation in the condenser and evaporator by matching the glides of refrigerant and heat transfer fluid. Glide matching is difficult with some zeotropic mixtures due to the nonlinear variation of enthalpy with temperature during phase change. Also, there is a distinct possibility of formation of pinch points with some mixtures, resulting in entropy generation. In this paper, the performance of four mixtures of R32, R134a, R125, R143a and R23 are studied as alternatives to R22 and R502 from thermodynamic as well as temperature pinch points of view. The results demonstrate the importance and the need for pinch point analysis in the evaluation of alternative zeotropic refrigerant mixtures.


๐Ÿ“œ SIMILAR VOLUMES


Performance enhancement of some alternat
โœ Samuel M. Sami; Daniel E. Desjardins ๐Ÿ“‚ Article ๐Ÿ“… 2000 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 133 KB

The results of an experimental study on the behaviour of some new alternatives to R-502 using heated suction accumulator are presented. The experimental set up was composed of a fully instrumented air}source heat pump with a capacity of 12 000 BTUH and equipped with a heated suction accumulator. Th

Performance comparative study of new alt
โœ Samuel M. Sami; Daniel E. Desjardins ๐Ÿ“‚ Article ๐Ÿ“… 2000 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 123 KB ๐Ÿ‘ 2 views

In this paper the test results of a performance evaluation of new alternatives; R-407B, R-507, R-408A and R-404A as substitutes to CFC-502 are presented. The test results were obtained using an air-source heat pump with enhanced surface tubing under standard ARI conditions. The data demonstrated th

Thermodynamic analysis of R422 series re
โœ Akhilesh Arora; H. L. Sachdev ๐Ÿ“‚ Article ๐Ÿ“… 2009 ๐Ÿ› John Wiley and Sons ๐ŸŒ English โš– 232 KB ๐Ÿ‘ 1 views

In the present study, the first and second law analysis of R422 series refrigerants (R422A, R422B, R422C and R422D) is presented as an alternative to HCFC22. A computational model, developed in engineering equation solver software, is employed for comparing the performance of these refrigerants in v