This paper briefly reviews CEGB fireside corrosion experience. It first summarises the numbers and operating conditions of the plants, and indicates the range of materials used in the boilers. Experience of furnace wall and superheatedreheater corrosion in coal fired plant is summarised, emphasising
Danish experience with fireside corrosion
โ Scribed by Steen Inselmann
- Book ID
- 102479366
- Publisher
- John Wiley and Sons
- Year
- 1988
- Tongue
- German
- Weight
- 262 KB
- Volume
- 39
- Category
- Article
- ISSN
- 0947-5117
No coin nor oath required. For personal study only.
โฆ Synopsis
Fireside corrosion has not been a severe problem in Danish power plants.
Furnace wall corrosion has only been seen in one unit caused by insufficient control of the burners.
High temperature corrosion has only been seen in units, where the final stage of superheaterheheater was placed in gas temperatures above 1300ยฐC or where the difference in tube length was too big. Since 1970 the final stages of superheater and reheater are made of X20CrMoV 12.1, which has showed excellent behavior.
For estimation of the remaining service life of superheater/reheater, they are examined after 100.000 h in service.
Die feuerseitige Korrosion
stellte in danischen Kraftwerken keine groaeren Probleme. Ofenwandkorrosion wurde nur in einem Falle festgestellt und war auf unzureichende Regelung der Brenner zuriickzufiihren. Hochtemperaturkorrosion trat nur in solchen Anlagen auf, wo die Endstufe des Uberhitzers bzw. des Erhitzers im Bereich von Gastemperaturen oberhalb 1300ยฐC lag oder wo der Unterschied der Rohrlangen betrachtlich war. Seit 1970 werden die Endstufen des Uberhitzers bzw. Erhitzers aus X20CrMoV 12.1 gefertigt, der sich ausgezeichnet bewahrt hat. Zur Ermittlung der Restlebensdauer werden der Uberhitzer bzw. Erhitzer nach 100000 Betriebsstunden inspiziert.