Application of the cut-off resonator for microwave monitoring of transformer oil
β Scribed by Boris Kapilevich; Anatoly Lipsky; Boris Litvak
- Publisher
- John Wiley and Sons
- Year
- 2010
- Tongue
- English
- Weight
- 670 KB
- Volume
- 53
- Category
- Article
- ISSN
- 0895-2477
No coin nor oath required. For personal study only.
β¦ Synopsis
Abstract
This paper describes a cutβoff resonator designed for testing transformer oil is proposed.The two kinds of transformer oil have been comparedββfreshβ (unused) and βoldβ (used) for a long period in realβworld conditions. The experimental setup has been designed and assembled on the basis of the cutβoff resonator with plastic tube containing the tested oil. There was observed the shift of resonance curves of the measured insertion losses between the βoldβ and the βfreshβ samples. Also, the βoldβ oil has higher insertion loss that is caused by increasing its loss tangent compared with the βfreshβ oil. These parameters can be used for estimating quality of the transformer oils. Β© 2010 Wiley Periodicals, Inc. Microwave Opt Technol Lett 53:66β68, 2011; View this article online at wileyonlinelibrary.com. DOI 10.1002/mop.25630