The use of aerosol fire extinguishing generators at rotogravure fed presses
✍ Scribed by Klaus P. Scheuermann; M. Modigell; Wolfgang Koch; Hanns-Jürgen Roßkothen; Jochen Schmidt
- Publisher
- American Institute of Chemical Engineers
- Year
- 1999
- Tongue
- English
- Weight
- 753 KB
- Volume
- 18
- Category
- Article
- ISSN
- 1066-8527
No coin nor oath required. For personal study only.
✦ Synopsis
Abstract
Comprehensive experiments have demonstrated that aerosol fire extinguishing systems with the components 'detection, fire alarm and control unit along with an extinguishing generator represent a safety component that reduces the risk of fire hazard. The new extinguishing concept based on the solid matter aerosol potassium carbonate with about 20 g of aerosol/m^3^, 2 s reaction time and a particle size distribution from 0.5 μn to 2 μm ensures safe extinguishing of fires in the area of ink troughs in rotogravure fed presses. Other investigations have shown that from the point of view of fire hygiene, the extinguishing aqent poses no hazard to the health of employees.