𝔖 Bobbio Scriptorium
✦   LIBER   ✦

The ac superposition method, a new hot-line diagnostic method for 6-kV XLPE power cables

✍ Scribed by Takao Kumazawa; Masahiro Hotta; Shinichi Sugiyama; Toshinari Hashizume; Tsuneo Tani


Publisher
John Wiley and Sons
Year
2000
Tongue
English
Weight
549 KB
Volume
130
Category
Article
ISSN
0424-7760

No coin nor oath required. For personal study only.

✦ Synopsis


Water trees are the most hazardous factor affecting the life of XLPE distribution cables and the major cause of insulation failure. It is well known that insulation failure causes stoppages in electrical service and requires extensive repair work. Up to now, deterioration of cable insulation has been diagnosed mainly by the dc leakage current method. However, application of this method for diagnostic measurements requires interruption of electrical service. Several types of hot-line diagnostic methods (including the dc component current and dc superposition methods) were developed to detect water tree deterioration. However, these methods have some shortcomings, such as being subject to effects of stray currents and the accuracy of measurements not being sufficiently high. Therefore, we have attempted to develop a new hot-line diagnostic method. We investigated whether the signals produced by superposition of voltages of various frequencies to the cover layer of energized cables were correlated with deterioration by the water treeing. As a result, we found that a deterioration signal of 1 Hz was observed when we superposed an ac voltage (commercial frequency u 2 +1 Hz) on the cover layer of cable where the water tree had occurred in the insulation.