This study investigates the effect of flow maldistribution on the thermal performance of a three-fluid crossflow heat exchanger by the numerical method. In the inlets of three fluid streams, this study considers four modes of flow nonuniformity arrangement by using three flow maldistribution models.
Some effects of air flow maldistribution on performance of a compact evaporator with R134a
β Scribed by David J. Timoney; Patrick J. Foley
- Publisher
- Elsevier Science
- Year
- 1994
- Tongue
- English
- Weight
- 501 KB
- Volume
- 14
- Category
- Article
- ISSN
- 0890-4332
No coin nor oath required. For personal study only.
β¦ Synopsis
An experimental facility has been constructed to enable the effects of air flow non-uniformity on the transfer performance of refrigerant evaporators to be investigated. This is based on an open-circuit wind tunnel, which is equipped with a single component traversing LDA system, capable of determining local mean velocities and turbulence levels. The refrigerant circuit uses R134a and has been designed to allow maximum flexibility in setting test conditions.
Preliminary results are presented from tests on a single circuit finned-tube evaporator with 33 tubes, 300 mm long, arranged in an in-line matrix 4 rows deep, with 25 mm spacing. The height of the fin block was 225 mm, the fin spacing and tube external diameter were 4 mm and 9.5 mm respectively.
Contrary to expectations, increases in heat transfer duty and overall heat transfer coefficients were recorded as air flow non-uniformities were artificially introduced, whilst a constant mean air velocity was maintained.