There is no doubt that increased application of sprinkler protection through a building can significantly reduce fire losses. In many compartment fires, the water damage is far more extensive than the flame damage. This paper examines the possibility of controlling the flow of water from sprinklers
Modelling the response of sprinklers in compartment fires
β Scribed by A. K. Gupta
- Publisher
- John Wiley and Sons
- Year
- 2001
- Tongue
- English
- Weight
- 120 KB
- Volume
- 25
- Category
- Article
- ISSN
- 0308-0501
- DOI
- 10.1002/fam.762
No coin nor oath required. For personal study only.
β¦ Synopsis
Abstract
Alpert's expressions are used extensively to calculate the maximum temperature and velocity in the ceilingβjet at any distance, r, from the fire axis. These expressions are valid for unconfined ceilings insofar as the environment outside the ceilingβjet is uniform in temperature and is atmospheric ambient. In compartments the outward flow of hot gases is checked by the presence of bounding walls and so a layer of hot gases is formed in the upper portion of the compartment. The environment outside the ceilingβjet is no longer ambient atmospheric. Expressions due to Alpert becomes unsuitable, unless the effects of the accumulated hot layer are included in these expressions.
The effect of the upper layer temperature has been taken by assuming that since the ceilingβjet is completely submerged in the upper hot gas layer, the entrained gases are drawn from this layer only instead of the ambient atmospheric air at T~β~. Thus T~β~ has been replaced by T~L~ in the Alpert's empirical expression for ceilingβjet temperatures. The proposed equation is then used to calculate the response time of sprinklers fitted in compartments of varying sizes. Calculations have been done for identical conditions to those employed by Evans and compared. Comparison has also been made with Cooper's LAVENT model predictions. The study shows that the present model is capable of predicting the maximum, as well as average, temperatures in the ceilingβjets submerged in the hot gas layer. Copyright Β© 2001 John Wiley & Sons, Ltd.
π SIMILAR VOLUMES
Sprinklers are commonly sited in the high headspace atrium of a building where such systems are required. It was questioned whether sprinkler heads would be activated in the case of a 5re. A 5re modelling technique was applied to estimate the actuation time of sprinkler heads located in the atrium c
The almoetone parameter hypothesis is applied to the two-compartment model in pharmacokinetice. If the model is represented by a difference equation, then ita coefficienta are highly correlated, aa WIM expected from the hypothesis.