Modelling the response of sprinklers in compartment fires

✍ Scribed by A. K. Gupta


Publisher
John Wiley and Sons
Year
2001
Tongue
English
Weight
120 KB
Volume
25
Category
Article
ISSN
0308-0501

No coin nor oath required. For personal study only.

✦ Synopsis


Abstract

Alpert's expressions are used extensively to calculate the maximum temperature and velocity in the ceiling‐jet at any distance, r, from the fire axis. These expressions are valid for unconfined ceilings insofar as the environment outside the ceiling‐jet is uniform in temperature and is atmospheric ambient. In compartments the outward flow of hot gases is checked by the presence of bounding walls and so a layer of hot gases is formed in the upper portion of the compartment. The environment outside the ceiling‐jet is no longer ambient atmospheric. Expressions due to Alpert becomes unsuitable, unless the effects of the accumulated hot layer are included in these expressions.

The effect of the upper layer temperature has been taken by assuming that since the ceiling‐jet is completely submerged in the upper hot gas layer, the entrained gases are drawn from this layer only instead of the ambient atmospheric air at T~∞~. Thus T~∞~ has been replaced by T~L~ in the Alpert's empirical expression for ceiling‐jet temperatures. The proposed equation is then used to calculate the response time of sprinklers fitted in compartments of varying sizes. Calculations have been done for identical conditions to those employed by Evans and compared. Comparison has also been made with Cooper's LAVENT model predictions. The study shows that the present model is capable of predicting the maximum, as well as average, temperatures in the ceiling‐jets submerged in the hot gas layer. Copyright Β© 2001 John Wiley & Sons, Ltd.


πŸ“œ SIMILAR VOLUMES


Optimal control of sprinklers in compart
✍ Abraham M. Hasofer; Mehmet A. Tat πŸ“‚ Article πŸ“… 1997 πŸ› John Wiley and Sons 🌐 English βš– 162 KB πŸ‘ 1 views

There is no doubt that increased application of sprinkler protection through a building can significantly reduce fire losses. In many compartment fires, the water damage is far more extensive than the flame damage. This paper examines the possibility of controlling the flow of water from sprinklers

Studies on thermal responses of sprinkle
✍ R. Yin; W.K. Chow πŸ“‚ Article πŸ“… 2001 πŸ› John Wiley and Sons 🌐 English βš– 227 KB πŸ‘ 1 views

Sprinklers are commonly sited in the high headspace atrium of a building where such systems are required. It was questioned whether sprinkler heads would be activated in the case of a 5re. A 5re modelling technique was applied to estimate the actuation time of sprinkler heads located in the atrium c

A Note on the Two-Compartment Model in P
✍ Professor. Dr. M. Masuyama πŸ“‚ Article πŸ“… 1988 πŸ› John Wiley and Sons 🌐 English βš– 251 KB πŸ‘ 2 views

The almoetone parameter hypothesis is applied to the two-compartment model in pharmacokinetice. If the model is represented by a difference equation, then ita coefficienta are highly correlated, aa WIM expected from the hypothesis.