𝔖 Bobbio Scriptorium
✦   LIBER   ✦

DC interruption characteristic of vacuum circuit breaker

✍ Scribed by Hiromi Odaka; Masataka Yamada; Ryohei Sakuma; Cuie Ding; Eiji Kaneko; Satoru Yanabu


Book ID
102159266
Publisher
John Wiley and Sons
Year
2007
Tongue
English
Weight
487 KB
Volume
161
Category
Article
ISSN
0424-7760

No coin nor oath required. For personal study only.

✦ Synopsis


Abstract

A high‐speed vacuum circuit breaker (HSVCB) has been investigated. HSVCB makes high‐frequency current superimposed on a fault current so that the current is forced to be zero and is interrupted. Its interruption performance is considered to be dependent on the rate of change of the current (di/dt). As a fundamental research, we investigated the di/dt– dv/dt characteristics and the insulation recovery characteristic after interrupting the counter‐pulse current for various contact materials of AgWC, CuW, and CuCr. The results revealed that the case where the gap length is larger is better in a current interruption performance. Moreover, it was found that di/dt is not dependent on the insulation recovery characteristics, but the magnitude of interruption current is of great influence. Β© 2007 Wiley Periodicals, Inc. Electr Eng Jpn, 161(1): 17– 25, 2007; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20362