Correlation of damage in Copper Potable Water Installations with laboratory data with emphasis on operating conditions and design parameters

✍ Scribed by Dr. D. Wagner; Dipl.-Ing. H. Peinemann; Dipl.-Ing. H. Siedlarek; Prof. Dr. W. R. Fischer


Publisher
John Wiley and Sons
Year
1996
Tongue
German
Weight
733 KB
Volume
47
Category
Article
ISSN
0947-5117

No coin nor oath required. For personal study only.

✦ Synopsis


Abstract

Microbial influenced corrosion (MIC) occurred in copper drinking water installations of a water distribution area in Germany in a number of mainly institutional buildings. The extent of the manifestations of corrosion typical for this process differed considerably although the operating time of the affected installations was comparable. This difference must have been caused mainly by operating conditions and design parameters since the composition of the potable water and the quality of the copper tubes did not vary. This question has been investigated by setting up two test rigs operating at ambient temperature in an institutional building whose copper installation was severely affected by MIC. The corrosion process was successfully simulated in these test rigs.

Corroded copper samples were taken from different house installations in this water distribution area and from the test rigs. The copper pipes of the different sources were inspected with respect to different operating conditions and design parameters. The obtained results cover the spectrum of the extent of the manifestations typical for this MIC process. Besides an induction period, a seasonal influence was evaluated for one institutional building.