## Abstract A copper corrosion process of unknown origin in a county hospital in Germany has been observed in the cold and warm water supplies shortly after operating the hospital. It seemed that the cause of these damages could be attributed to microbially induced corrosion. The evaluation of dama
Copper deterioration in a water distribution system of a county hospital in Germany caused by microbially induced corrosion – I. Description of the problem
✍ Scribed by W. Fischer; H. H. Paradies; D. Wagner; I. Hänßel
- Publisher
- John Wiley and Sons
- Year
- 1992
- Tongue
- German
- Weight
- 911 KB
- Volume
- 43
- Category
- Article
- ISSN
- 0947-5117
No coin nor oath required. For personal study only.
✦ Synopsis
Abstract
A severe copper corrosion process in the water distribution system of a County Hospital has been detected in the cold and warm water sections shortly after the opening of the Hospital. The damaged copper pipes showed pitting corrosion phenomena that could not be attributed to known types of pitting. The results of a first sampling revealed the same kind of corrosion in all installation areas. A thorough examination of the samples (perforations and hole depths) proved an influence of design and operating conditions on the extent of corrosion.
The analysis of the corrosion products showed that some products could be attributed to microbial activities in the copper pipes. A polymeric layer, the so‐called “biofi”, could be detected beneath the corrosion products. The presence of a biofilm indicates microbially induced corrosion. First countermeasures are being taken in the County Hospital to prevent further damages.