Copper deterioration in a water distribution system of a county hospital in Germany caused by microbially induced corrosion – I. Description of the problem

✍ Scribed by W. Fischer; H. H. Paradies; D. Wagner; I. Hänßel


Publisher
John Wiley and Sons
Year
1992
Tongue
German
Weight
911 KB
Volume
43
Category
Article
ISSN
0947-5117

No coin nor oath required. For personal study only.

✦ Synopsis


Abstract

A severe copper corrosion process in the water distribution system of a County Hospital has been detected in the cold and warm water sections shortly after the opening of the Hospital. The damaged copper pipes showed pitting corrosion phenomena that could not be attributed to known types of pitting. The results of a first sampling revealed the same kind of corrosion in all installation areas. A thorough examination of the samples (perforations and hole depths) proved an influence of design and operating conditions on the extent of corrosion.

The analysis of the corrosion products showed that some products could be attributed to microbial activities in the copper pipes. A polymeric layer, the so‐called “biofi”, could be detected beneath the corrosion products. The presence of a biofilm indicates microbially induced corrosion. First countermeasures are being taken in the County Hospital to prevent further damages.


📜 SIMILAR VOLUMES


Copper deterioration in a water distribu
✍ Dr. D. Wagner; Prof. Dr. W. Fischer; Prof. Dr. H. H. Paradies 📂 Article 📅 1992 🏛 John Wiley and Sons 🌐 German ⚖ 783 KB

## Abstract A copper corrosion process of unknown origin in a county hospital in Germany has been observed in the cold and warm water supplies shortly after operating the hospital. It seemed that the cause of these damages could be attributed to microbially induced corrosion. The evaluation of dama