๐”– Bobbio Scriptorium
โœฆ   LIBER   โœฆ

An automatic noncontact measurement technique for investigation of the effect of frosting on wind convector heat transfer performance

โœ Scribed by P.F. Monaghan; M. Redfern; P.H. Oosthuizen; F.W. Grealish; D.P. Finn


Book ID
103926869
Publisher
Elsevier Science
Year
1991
Tongue
English
Weight
685 KB
Volume
4
Category
Article
ISSN
0894-1777

No coin nor oath required. For personal study only.

โœฆ Synopsis


This paper describes the design, testing, and performance of a computer vision/load cell system for automatic measurement of mass and depth of frost accumulated on heat exchangers located outdoors. Frost mass accumulation of up to 10 kg and frost depths of up to 12 mm have been recorded in test runs of up to 24 h. The uncertainty for these measurements is + 0.016 kg and ___ 0.1 mm, respectively. Data on heat transfer rates and weather conditions are also logged automatically. Frost layer development outdoors and its effect on heat transfer do not always follow the same trends found for frosting in steady laboratory conditions.