Experiments are conducted to determine the effect of dimensionless parameters on heat-transfer characteristics of a vertical flat thermosyphon (VFT). The VFT used in this study employed a copper tube with an inner diameter of 8.6 mm. The cross-sectional areas of the tube were reduced by pressing the
A correlation to predict heat-transfer rates of a two-phase closed thermosyphon (TPCT) using silver nanofluid at normal operating conditions
✍ Scribed by T. Parametthanuwat; S. Rittidech; A. Pattiya
- Publisher
- Elsevier Science
- Year
- 2010
- Tongue
- English
- Weight
- 877 KB
- Volume
- 53
- Category
- Article
- ISSN
- 0017-9310
No coin nor oath required. For personal study only.
✦ Synopsis
The effect of using silver nanofluid (de ionized water mixed with silver nano and particles less than 100 nm) on the thermal characteristics of a two-phase closed thermosyphon in an operating state was investigated in this research. The thermosyphon was made with copper tubes with 7.5, 11.1 and 25.4 mm ID. The filling ratios of 30%, 50% and 80% by evaporator length and aspect ratios of 5, 10, and 20 with an inclination angle 90°. The operating temperatures were 40 °C, 50 °C and 60 °C. The research reports the effect of dimensionless parameters on heat-transfer characteristics were: Le d i , Bo, Pr, We, Fr, Ja, Co, Nu, Ar, Gr and Ku. It was found that the filling ratio has no effect on the ratio of heat-transfer characteristics in the vertical position, but the properties of the working fluid affected the heat-transfer rate. In addition a correlation for predicting the heat flux for the two-phase closed thermosyphon in the vertical position has been established.